In order to facilitate heat dissipation and equipment maintenance, it is recommended that the distance between the front and rear of the cabinet and the wall or other equipment should not be less than 1 meter, and the clear height of the equipment room should not be less than 2.
For battery racks, there shall be a minimum clearance of 25 mm (1 in.) between a cell container and any wall or structure on the side not requiring access for maintenance. Battery stands shall be permitted to contact adjacent walls or structures, provided that the battery shelf has a free air space for not less than 90 percent of its length.
Spaces about battery systems shall comply with 110.26. Working space shall be measured from the edge of the battery cabinet, racks, or trays. For battery racks, there shall be a minimum clearance of 25 mm (1 in.) between a cell container and any wall or structure on the side not requiring access for maintenance.
A protection device must be sized properly so that the energy flowing from the batteries during the failure will not cause damage to the batteries or other components along the short circuit path. The protection must clear the fault in less than 100 milliseconds. The impedance of the line is mainly resistance and inductance.
Battery locations shall conform to 480.9 (A), (B), and (C). (A) Ventilation. Provisions appropriate to the battery technology shall be made for sufficient diffusion and ventilation of gases from the battery, if present, to prevent the accumulation of an explosive mixture. (B) Live Parts. Guarding of live parts shall comply with 110.27.
Can a protection device trip a battery?
The selected protection device must trip in case of a fault in less than 100 ms. In case the fault current provided by the battery does not allow for the finding of protection devices, such as a Circuit Breaker or fuse, that meets the derating criteria stated in point B, it is hence possible to increase the multiplier up to 0.7.
Can a battery stand contact a wall?
Battery stands shall be permitted to contact adjacent walls or structures, provided that the battery shelf has a free air space for not less than 90 percent of its length. (D) Top Terminal Batteries.